Interstate standard

Passenger elevators
And freight

Technical conditions

Interstate Council
According to standardization, metrology and certification
Minsk

Preface

1 Developed by TC 209 "Elevators and Building Lifts"

Submitted by the State Standard of Russia

2 Adopted by the Interstate Council for Standardization, Metrology and Certification (Protocol No. 8-95 of October 12, 1995)

Name of state

Name of the National Standardization Authority

The Republic of Azerbaijan

Azgosstandard

Republic of Belarus

Belstandard.

The Republic of Kazakhstan

Gosstandart of the Republic of Kazakhstan

Kyrgyz Republic

Kyrgyzstandard

The Republic of Moldova

Moldova Standard

the Russian Federation

State Standard of Russia

The Republic of Tajikistan

Tajik State Center for Standardization, Metrology and Certification

Turkmenistan

Home State Inspectorate of Turkmenistan

The Republic of Uzbekistan

UZGOSSTANDART

State Standard of Ukraine

3 Resolution of the Committee of the Russian Federation on Standardization, Metrology and Certification of February 15, 1996 No. 68 Interstate Standard 22011-95 was performed directly as state Standard Of the Russian Federation from January 1, 1997

5 reprint

Passenger and freight elevators

Technical conditions

Passenger and Goods Lifts. Specifications.

Date of introduction 1997-01-01

1 AREA OF USE

This standard applies to electric passenger, hospital, cargo and cargo small elevators (hereinafter - elevators).

Standard does not apply to elevators:

Freight paving;

Ship;

Special purpose;

For work in buildings and premises related to categories A and B * in the explosion and fire hazard;

To work in premises with aggressive pairs or gas gases;

To work in conditions of moisture condensation in a mine or machine room, loss of inlet or ice formation on equipment.

* Categories of buildings and premises in the explosion and fire hazard are determined at the design stages of buildings and structures in accordance with the requirements of national fire hazard.

The requirements of this standard are mandatory.

Mandatory requirements for the quality of elevators that ensure their safety for the life, health and property of the population, environmental protection are set out in Section 5.

2 Regulatory references

The main parameters and dimensions of electrical freight elevators - according to GOST 8823.

The main parameters and the size of electrical cargo small elevators - according to GOST 8824.

The symbol of elevators is given in Appendix A.

4 Technical requirements

4.1 Characteristics

4.1.1 Elevators must comply with or exceed the requirements of this Standard, "rules of device and safe operation of elevators" of national technical supervision authorities for the safe operation of elevators (hereinafter referred to as Pubel Gosgortecadzor) and "Rules of electrical installation devices" of the Ministry of Fuel and Energy.

4.1.2 Installation of elevators for work in buildings and premises related to the explosion and fire hazard to category B should be carried out in accordance with the requirements of national building standards and rules for elevators of this category.

4.1.3 Installation of elevators in buildings and structures located in areas with the intensity of seismic exposure 7-9 points is allowed when performing requirements that take into account the conditions of operation specified in the regulatory or design documentation.

4.1.4 The values \u200b\u200bof the elevator indicators must correspond to those shown in Tables 1 and 2.

4.1.5 The elevators should work in the operational modes indicated in Table 3, and maintain a healthy state at a height above sea level up to 2000 m.

When operating the elevator at height above sea level from 1000 to 2000 m, the number of inclusions per hour is reduced by 1% each 100 m.

4.1.6 Elevators are manufactured to work from an AC network with a frequency of 50 Hz and a voltage of 380 V.

Table 1

Name of the indicator

Passenger elevators

for residential buildings

for public buildings and buildings of industrial enterprises

for industrial buildings

hospital

Nominal speed, m / s

Assigned service life, years

Stop accuracy of elevator cabins, mm, driven:

Adjustable

Unregulated

BUT, no more

Sound level in the cockpit when opening and closing doors, dB BUT,no more

Vibrating the floor of the cab floor with the steady movement, m / s, not more

Corrected sound power level winch, dB BUT, not less

Load capacity, kg.

800; 1000; 1250; 1600

Note - At the end of the appointed service life, the elevator conducts it to be examined in accordance with the procedure established by the Gosgortkhnadzor.

table 2

Name of the indicator

Freight elevators

Nominal speed, m / s

Average work on failure, h, not less

Assigned service life, years

Sound level in the cockpit when installed movement, dB BUT, no more

Vibration, m / s, no more

Corrected sound power level winch, dB BUT, no more

Load capacity, kg.

2000 or more

* For elevators with a carrying capacity of 5000 kg.

** For elevators with a carrying capacity of 4000 and 6300 kg.

Note - At the end of the appointed service life, the elevator conducts it to be examined in accordance with the procedure established by the Gosgortkhnadzor.

Table 3.

Nominal speed, m / s

Operating mode

Number of inclusions per hour, no more

Relative duration of the inclusion of PV,%, not more

Passenger

for residential buildings

for buildings of public and industrial enterprises

hospital

for industrial buildings

Cargo

released, with Monorail

Cargo small

* For elevators with a carrying capacity of St. 630 kg

Table 4.

Type of climatic execution

Limit operating temperatures, ° С

Top value of relative humidity

machine room

Passenger

for residential buildings, public and industrial enterprises, hospital

From +40 to +1

80% at + 25 ° С

80% "+ 25 ° С

From +55 to +1

98% at + 35 ° С

98% "+ 35 ° С

for industrial buildings

From +40 to -40

98 % at + 25 ° С

80% "+ 25 ° С

Cargo

normal, extrusive, with monorail

From +40 to -20

98% at + 25 ° С

98% "+ 25 ° С

From +45 to -10

98% at + 35 ° С

98% "+ 35 ° С

Cargo small

From +40 to +1

80% at + 25 ° С

* When recording the climatic performance of the elevator, the category of its placement indicates the category of engine room location.

At the request of the customer, elevators can be made to work on the AC mains:

50 Hz frequency with voltage 240 and 415 V;

The frequency of 60 Hz "220; 230; 380; 400; 415 and 440 V.

The elevators should be operational when they are connected to the AC network with deviations from their nominal current frequency values \u200b\u200bof no more than 1% and voltage no more than 10%.

4.1.7 Radioomies arising from the function of the elevator should not exceed the values \u200b\u200bestablished by GOST 23511 and the national norms of admitted industrial radio interference. The tension of the radiopomech field created by the elevator is not normalized.

4.1.8 Elevators, depending on the operating conditions, the climatic executions and placement categories should be made (according to GOST 15150) shown in Table 4.

4.1.9 Cabs of freight elevators with solid doors, except for elevators with external control, as well as cabins of passenger elevators for residential and public buildings and buildings of industrial enterprises should have natural ventilation.

Cabins of passenger, hospital and freight elevators (with conductor) with solid doors in tropical versions should have natural and forced ventilation.

4.1.9.1 Passenger elevators with automatic doors with a speed of 1.0 m / s and more should have a fire danger mode, which is included in the signal on the signal from the automatic fire alarm systems and providing, regardless of loading and directions of the cabin, return Its on the main planting area, opening and holding in the open position of the doors of the cabin and mines.

4.1.9.2 Passenger elevators intended to transport fire units should have the operation of "transportation of fire divisions". The transfer of the elevator control to this mode should be carried out from the cab, while the control system should provide the elevator only on the clause orders.

4.1.10 Facing the cabin of the cabin, plafoons, flooring, as well as the buttons of orders and call posts, should be made from non-combustible or hard-scale materials.

4.1.11 In the roof of the cabin of the elevator used to transport fire units, the hatch should be provided with a size of at least 700x500 mm. Luke must be equipped with a switch controlling its locking.

4.1.12 The doors of the elevator mine must be fire-based second-type and meet the requirements of SNiP 21-01 (sections 3 and 4).

Fire Resistance Limit Mine passenger elevator For residential buildings at a speed of up to 1.0 m / s. Not installed.

The doors of the cargo elevator shaft are allowed not to equip the device for self-blocking.

Cargo small elevators with two stops is allowed to be executed in a metal frame mine with a fencing of metal sheets. At the same time, fire-prevention requirements for shaft doors are not presented.

4.1.13. The electrical drive system and the elevator automation should provide the ability to connect external elevator operation systems and establishing its faults.

Requirements for devices and alarm elevator - according to GOST 28911. When installing a group of two and more passenger elevators having the same rated speed and, as a rule, the number of stops must be applied to the group control system with a common control device for control on each planting area.

4.1.14 Signal colors and safety signs - according to GOST 12.4.026 and GOST 28911, respectively.

Wherein:

Oil surfaces, caps, drain traffic, oil indicators should have a red coating;

The surface of the rotation parts, not closed with a cover, except for the surfaces of the rotation parts on the tensioning device of the speed limiter and counterweight, should have a yellow coating.

It is allowed to paint the end surfaces of the rotation parts in the form of an annular strip of a width of at least 20 mm in accordance with the place of color in the drawings.

Passenger elevators that have the work of "Transportation of fire units" should have a distinctive symbolism located on the main seating area, in accordance with the instructions of the design documentation.

4.1.15 Technical documentation for the elevator must comply with the requirements of the elevator design project, approved in the prescribed manner.

4.1.16 Painted surfaces of the surfaces of elevator equipment must correspond to the coating classes specified in Table 5.

Table 5.

Name of surface with paint and varnish

The surface of the components of the elevator, located in a mine, machine and block room, including:

External surfaces of the fence cabins (shields);

Non-sash cabinets of cabin doors and mines;

Guides and counterweights, except for the working surface of the head of the guide profile;

Details (except fastening) and assembly units of fastening of guide cabins and counterweight;

Cabs and counterweight frame surfaces, shunt brackets and sensors in the mine and on the cabin, metal structures of blocks, buffers, tensioning devices, transformers and other electrical equipment, frame and subframes winch;

Unprocessed surfaces of blocks and pulleys, grounding tires;

Cast iron cargoes of counterweight and tensioning rope device, speed limiter

The inner surfaces of the cabin of passenger elevators, not visible from the inside of it. The inner surface of the cab of the cargo elevators visible from the inside.

Unprocessed gear surfaces, steering wheel, winch brakes, speed limiter, hydraulic buffer

The inner surface of the passenger elevator cabin visible from the inside of it.

The front surfaces of the doors of the cabin and shaft, if they do not have another decorative finish

IV, III (at the request of the customer)

Metal coatings must correspond to GOST 9.301. The painting of equipment for elevators of tropical climatic execution - according to GOST 9.401.

4.1.17 The equipment of the freight elevator in agreement with the customer is allowed to cover the primer with the subsequent color after the installation.

It is allowed no color in hard-to-reach places.

Inaccessible places should be indicated in the design documentation.

Cast iron of the counterweight and the stretch device of the elevator speed limiter is allowed not to cover.

4.1.18 The front side of the mine door sashs of one or more elevators should have on each stopping platform the coating of one color and one shade, if there is no other customer requirement.

4.1.19 Welding Places (Welded Sews and Oil Surfaces), made when installing the elevator, should be protected by the coating provided for them in the technical documentation for the elevator.

4.1.20 The ropes must be a dimensional length of one bay and with a purified surface. Dirt and other inclusions on the surface of the ropes are not allowed.

The ends of the ropes should be protected from spinning, and the sections of the cut is made in accordance with 2.1.9 GOST 3241.

4.1.21 Suspended electrical elevator cable must be broken, with closer and installed wires.

Wires of wiring harnesses, laid in the mine and machine room, must be marked. In coordination with the customer, the delivery of measuring length wires is allowed.

4.1.22 Requirements for welded assembly units, castings from ferrous metals, aluminum and highly aluminous bronze, details of plastic materials, mechanically processed parts, heat treatment, as well as requirements for components of elevators - according to them by regulatory and technical documentation (NTD) .

4.2 Completeness

4.2.1 The elevator must include:

Elevator equipment in accordance with the specification on the elevator, incl. Spare parts and materials designed for the warranty period of the elevator, tools and accessories (zip) required for maintenance and repair of the elevator; Spare products for commissioning work during installation (winters) in accordance with their Vedomosti;

Technical documentation sent with elevator and list of parts for replacement in accordance with applications B and in respectively.

In the case of sending several elevators of one type, type, load capacity, speed and execution (various arrangements of the counterweight, passing or non-passing cabin, etc.) for installation on one object or building, the technical documentation is sent in one instance by 5 elevators. Passport, conceptual electrical circuit, electrical connections, mounting (installation) drawing should be sent with each elevator.

4.2.2 Composite parts of the elevator: winch, cab, Mine doors, hydraulic buffer, speed limiter, the tensioning device should be sent in the assembled and adjusted form if there is no other customer requirement.

Brackets of fastening of storey switches, shunts, selection sensors, storey terminal boxes should be sent with attached clamps. Details of the fastening of the guides should be sent in the assembled form with attached clamps.

4.2.3 In disassembled form, it is allowed to send:

Counterweight;

Cabin of a cargo elevator with dimensions in terms of 1500x2000 mm and more;

Cabin of the hospital elevator for buildings of medical and prophylactic institutions;

Doors of the cargo elevators with width of the opening of more than 2000 mm or a height of more than 2600 mm;

Framing (with its own) openings of passenger elevators.

4.3 Marking

4.3.1 Each elevator must be equipped with a signboard made according to GOST 12969, GOST 12970 and GOST 12971.

The elevator plate should indicate:

Name or trademark of the elevator manufacturer;

Lifting equipment marking for the regions of the Far North of the Russian Federation and hard-to-reach areas (for example, mountain, etc.) - according to GOST 15846.

4.4 Packaging

4.4.1 Composite parts of the elevator equipment before packaging must be canned.

Temporary anti-corrosion protection - according to GOST 9.014.

The use of conservation oils for conservation of ropes is not allowed. Their use is allowed to cover the surface of the guide tagging profile.

The preservation of components of elevator equipment should ensure their protection to the first subcast: component parts of the elevator - up to one year, spare parts - up to 2.5 years. The renouncer should hold the elevator owner.

The packaging sheets should indicate: the date and period of the reconstruction, as well as means of temporary corrosion protection.

4.4.2 Preservation and packaging of wires and cables should be carried out with regard to the requirements of GOST 18690, electrical equipment (including bundles) - according to GOST 23216.

4.4.3 Packaging of equipment and technical documentation of the elevator - according to GOST 23170.

The ropes are packaged into a polymer film according to GOST 10354 or on another NTD, coordinated with the GOSGORTECHNADOR, or in waterproof paper according to GOST 8828 and GOST 515.

The rope shown in the bay must be tightly tied up with a soft wire (according to GOST 3282 or other NTD) or a strand of the same rope, or a tape according to GOST 3560 (or other NTD) at least four places that are evenly located around the circle.

4.4.4 Packaging Equipment Equipment in tropical climatic execution must comply with the requirements of GOST 24634, while Tara timber must be impregnated with antiseptic. It is allowed instead of the antiseptation of paint boxes in two layers of the gray paint of the PF-115 brand according to GOST 6465 or other similar paints.

4.4.5 Packaging Equipment Equipment sent to the regions of the Far North of the Russian Federation and hard-to-reach areas - according to GOST 15846.

5 Safety requirements

The safety of elevators is ensured by the implementation of the set of requirements 4.1.1-4.1.22 (except 4.1.15, 4.1.17-4.1.18, 4.1.21), sections 3, 5-7, 9 of this standard and Pubel Gosgortkhnadzor.

6 Rules acceptance

6.1 Composite parts (equipment) of the elevator (including Zip and Wali) should be subjected to acceptance control by the manufacturer's technical control service in order to determine their suitability for sending to the consumer.

6.2 Remote control of the components of the elevator should be statistical alternatively according to GOST 18242.

Parameters, dimensions, requirements to be controlled, sampling and types of defects should be indicated in the technical documentation for the elevator.

6.3 Acceptance control of component parts of the elevator should have the following control plan and acceptance level of defectiveness:

a) control plan:

Control level - II,

Type of control plan - single-stage,

b) acceptance level of winch defective, gearbox (if it is produced as a spare part), elevator doors drive, speed limit, catcher, hydraulic buffer, cab loading devices, shaft doors, cabin doors, springs of responsible destination (buffer springs, brakes, trappers , cab pendants and counterweight, etc.), zip and winters:

2.5% - for significant defects;

6.5%-for insignificant defects.

Remote defectiveness assembly units And equipment details:

0% - for critical defects;

6.5% - for significant defects.

Production cycle with continuous statistical control - one year.

6.4 Purchased products, materials and raw materials should be subjected to input control according to GOST 24297.

When input control, the low-voltage complete device (HCC) must be checked for operation.

Upon admission from the Customer or consumer elevators of advertising or claims to the quality of the purchase product, the elevator manufacturer during input control should use another more stringent type of control according to GOST 18242.

6.5 Composite parts of the elevator, details and castings produced by other manufacturers should be subjected to an elevator manufacturer to visual control to detect possible damage to this equipment during transportation.

Manufacturer of equipment, details and castings upon receipt of claims from the elevator manufacturer must for 3 days to inform it about the decision to eliminate the defect.

6.6 Acceptance tests of component parts (equipment) elevator

The components of the elevator mentioned in 6.3 should be subjected to acceptance tests of its manufacturer on programs and methods approved in the prescribed manner.

The size of the sample of the samples of the components of the elevator is set by the elevator manufacturer and is indicated in the technical documentation.

6.7 Elevators of each model must be trial:

After making a prototype:

Preliminary;

Acceptable;

When developing production - qualifying;

With serial production:

Acceptance tests of component parts of the elevator;

Periodic;

Typical.

6.8 The frequency of testing of the elevator listed in 6.7, the number of elevators to be subjected to these tests, and the number of elevators in the batch, from which the test elevator is selected, must correspond to Table 6.

6.9 Periodic Tests

6.9.1 Periodic elevator tests are carried out in order to verify the stability of the quality of manufacturing and the possibility of continuing its release.

Periodic tests should include verification of all mandatory requirements established by this standard and Pubel Gosgorekhnadzor.

6.9.2 With unsatisfactory results of periodic tests, at least one of the items of the program should be repeated tests on these points on the double number of relevant component parts Elevator taken from the same party. Results of repeated tests are final.

Table 6.

Type of test

Test frequency

Number of elevators

The number of elevators in the party, from which the elevators are taken for testing

Preliminary

One-time - after the manufacture of prototypes

All experimental elevator samples, the number of which is determined by the technical assignment to the development

Remote

All experienced samples that have passed preliminary tests.

Qualification

When setting the elevator production of this model

At least 3.

Periodic

At least once every three years

At least 7 *

Every time the design change

At least 3.

* When conducting tests, the manufacturer of the elevators is selected from among the past acceptance control and ready to send to the consumer. When conducting tests on the object of operation, taken from the number made by no more than 18 months before the test.

7 Monitoring methods

7.1 Measurement Requirements

7.1.1 Measurement tools must be believed in accordance with the requirements of GOST 8.002 and GOST 8.513.

Testing equipment must be certified according to GOST 24555, non-standardized measurement tools must undergo metrological certification according to GOST 8.326.

7.2 Preparation for Testing

7.2.1 Before carrying out acceptance and qualification tests of the elevator, tests for the reliability of the winch, drive doors, cabin doors, shaft doors, speed limit, trappers, hydraulic buffers, booth loading devices.

It is allowed not to test the reliability of the equipment borrowed from other elevators, provided that it has been tested earlier and on it, the manufacturer has an rationale for maintaining reliability indicators under operating conditions.

The low-voltage complete device must have a document confirming its reliability.

7.2.2 Prior to periodic tests, the manufacturer must submit materials confirming the reliability indicators of elevators.

Confirmation of reliability indicators is carried out on the basis of a test for the reliability of the elevator or its component parts (equipment) in the period between periodic tests or by the results of operational observations of the work of similar elevators.

Methods and plans for reliability and observations during operation - according to GOST 27.410.

7.2.3 For standard elevator tests, which uses equipment with changes that can affect technical characteristics Elevator and / or its operation must be trials of each modified equipment.

With positive results of testing modified equipment, typical elevator tests are allowed.

7.3 Elevator testing

7.3.1 The tests of elevators should be carried out in accordance with the programs and methods of tests, coordinated in the prescribed manner.

7.3.1.1 Before the start of the elevator test, the manufacturer must have a "act of technical readiness of the elevator".

Tests should be carried out on the territory of the manufacturer of elevators. The test of the elevator at the operating facility should be coordinated with the Gosgortkhnadzor.

It is not allowed to replace the elevator tests by testing its layout.

When testing group control of elevators at three or more elevators, this system is allowed in the group.

When testing several elevators of the same type and type, it is allowed to determine the quantitative and qualitative characteristics of a single elevator - a typical representative of the group (determined by the elevator developer). The remaining elevators of the group should be checked characteristics that differ from the characteristics of a typical representative.

With unsatisfactory test results for one or more indicators, the resumption of repeated tests is allowed only after establishing the causes of deficiencies and eliminate them.

8 Transportation and storage

8.1 Transportation of equipment equipment is allowed to carry out any kind of transport in accordance with the rules operating on them.

When transporting elevator equipment on the decks of vessels, the elevator manufacturer must take into account the effect of the atmosphere of type III according to GOST 15150.

8.2 Terms and Terms of Storage and Transportation of Equipment Equipment, Zip and Waline in Packaging and / or Conservation Manufacturer must comply specified in Table 7.

Table 7.

Climatic performance of the elevator according to GOST 15150

Equipment elevator

mechanical with installed electrical equipment

mechanical without electrical equipment

Zip and Zim.

2 - a group of conditional designation of the basic parameters of the elevator (carrying capacity and rated speed), installed in accordance with the methodology operating in the lift construction of the CIS countries;

3 - An indication of the installation of an elevator - single (in the case notation does not indicate), group (g) from group 2 - 4, 6 elevators (g2 - g4, g6);

4 - the number of elevator stops;

6 -

7 - indication of the presence of a modulation of the elevator "Transportation of fire units" (P);

8 -

An example of the conditional designation of a passenger elevator for residential buildings with basic sizes and constructive design according to GOST 5746, with a carrying capacity of 400 kg, with a rated speed of 0.71 m / s, a single installation, with a number of stops 10, performed for operation in a moderately cold climate , placement categories 4 and in the area with the intensity of seismic impact of 8 points that does not have a mode of operation "Transportation of fire units":

2 scheme of conditional designation of freight elevators

1 - type and type of elevator with parameters, primary sizes and constructive design according to GOST 8823:

Lift cargo regular (lgo);

Freight release elevator (LGV);

Freight elevator usual with monorail (LGOM);

2 - the sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - indication of the gauze of the cabin in terms of the elevator of this carrying capacity - the first (smaller - in the conditional designation does not indicate) or the second (greater) (b);

8 - view of the cab - the passage (Ave.), non-volume (neop.);

10 - An indication of the execution of the elevator (the execution without taking into account the seismic effects in the conditional designation does not indicate), which takes into account the seismic impact (C) with the intensity of 7 - 9 points (C7 - C9);

11 - Designation of this Standard.

An example of the conditional designation of a truck conventional elevator with basic sizes and constructive design according to GOST 8823, with ordinal registration number 922, with a carrying capacity of 1000 kg, at a rated velocity of 0.4 m / s, lifting height 60 m, with a number of stops 16, with a passing cabin of the second dimension, for operation in a moderately cold climate and placement category 4:

3 scheme of the conditional designation of cargo small elevators

1 - type of elevator; LGM - freight elevator small with parameters, basic sizes and constructive design according to GOST 8824;

2 - sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - view of the cab - Through (SLE.), Non-cut (narrow);

9 - Designation of this Standard.

An example of the conditional designation of a cargo small elevator with parameters, the main dimensions and constructive design according to GOST 8824, with the registration number of the model 958, with a carrying capacity of 100 kg, at a rated speed of 0.4 m / s, a lifting height of 45 m, with a number of stops 14, with no shortcut The cabin, performed for operation in the zone of moderately cold climate and with the category of placement 4:

Appendix B.

(mandatory)

List of a set of technical documentation *

* Depending on the type and type of specific elevator, the list of documents for its equipment is specified by the developer.

The technical documentation of the elevator includes the following documents:

Elevator Passport according to Pubel Gosgortecadzor with documents certifying quality: winches, speed limit, doors drive, hydraulic buffer, springs of cabins and counterweight, brake springs, trap springs. NCU passport (stored with the elevator passport);

Mounting drawing (installation drawing, the sample of which is agreed with the Gosgortkhnadzor) (2 copies);

Installation instructions, start-up, regulation and running;

Technical description and instruction manual;

A conceptual electrical circuit with a list of elements (3 copies);

Description of the electric drive and automation (allowed to be supplied as part technical description and operating instructions);

Electrical diagram of the electrical components of the elevator control (comes with the NCU);

Electrical diagram of elevator compounds;

Vedomosti Zip and winters;

Drawings of parts for replacement (see Appendix B);

Assembly drawings (and specification) Elevator equipment for: speed limiter, hydraulic buffer, winch, gearbox, brake, coupling, tap block, cabin, catcher, automatic door drive, minor door, automatic and manual shaft door locks, wire wiring Machine room, shaft and cabin, counterweight.

Appendix B.

List of parts for replacement *

* The parts indicated in the list are designed to replace failed (wear, breakage) during the period of the elevator after the expiration of its warranty period

Pulleys canned.

Brake block assembly.

Spring brakes.

Cabin sliding shoe liner.

Roller (rollers) Cabin shoe.

Insert of the sliding door of the cab of freight elevators.

Passenger lifts shoe shoes.

Roller of the door of the cabin of freight elevators.

Passenger lift carriage carriage roller.

The roller drove the drive of the doors of passenger elevators.

Rubber stop drive doors.

The liner of the sliding shoe counterweight.

Roller carriages of automatic sliding doors of the mine.

Roller Ogrushed Mine Door Castle.

Pulley speed limiter.

Block of tap traction ropes of elevators.

Cleaves of clinorem transmission of cabin drives.

Ring Rubber Cabin Mobile Field Loading Device.

Cabin door drive belt.

Note - The list of parts is specified for a particular elevator by its developer.

Keywords: passenger, cargo and cargo lifts Small elevators, technical requirements, security requirements, acceptance rules, transportation and storage

1 area of \u200b\u200buse. one

3 Main parameters and sizes .. 3

4 Technical requirements. 3.

4.1 Characteristics. 3.

4.2 Completeness. eight

4.3 Marking. nine

4.4 Packaging. nine

5 Safety requirements. nine

6 acceptance rules. nine

6.6 Acceptance tests of components of the elevator components (equipment). 10

6.9 Periodic tests. eleven

7 Control methods. eleven

7.1 Measurement Requirements. eleven

7.2 Preparation for testing .. 11

7.3 Conducting elevator tests. 12

8 Transportation and storage. 12

9 Installation and operation instructions. 13

10 manufacturer's guarantees. 13

application And the schemes for constructing the conditional designation of electric passenger, cargo and small freight elevators. 13

application B list of a set of technical documentation. fourteen

application In the list of parts for replacement .. 15

GOST 22011-95

Interstate standard

Passenger elevators
And freight

Technical conditions

Interstate Council
According to standardization, metrology and certification

Minsk

1998

Preface

1 Developed by TC 209 "Elevators and Building Lifts"

Submitted by the State Standard of Russia

2 Adopted by the Interstate Council for Standardization, Metrology and Certification (Protocol No. 8-95 of October 12, 1995)

Name of state

Name of the National Standardization Authority

The Republic of Azerbaijan

Azgosstandard

Republic of Belarus

Belstandard.

The Republic of Kazakhstan

Gosstandart of the Republic of Kazakhstan

Kyrgyz Republic

Kyrgyzstandard

The Republic of Moldova

Moldova Standard

the Russian Federation

State Standard of Russia

The Republic of Tajikistan

Tajik State Center for Standardization, Metrology and Certification

Turkmenistan

Home State Inspectorate of Turkmenistan

The Republic of Uzbekistan

UZGOSSTANDART.

Ukraine

State Standard of Ukraine

3 Resolution of the Committee of the Russian Federation on Standardization, Metrology and Certification of February 15, 1996 No. 68 Interstate Standard 22011-95 was enacted directly as the State Standard of the Russian Federation from January 1, 1997.

4 instead of GOST 22011-90

5 reprint

Interstate standard

Passenger and freight elevators

Technicalconditions

Passenger and Goods Lifts. Specifications.

dateadministration 1997-01-01

1 AREA OF USE

This standard applies to electric passenger, hospital, cargo and cargo small elevators (hereinafter - elevators).

Standard does not apply to elevators:

Passenger at rated speed (hereinafter referred to as speed) 2.0 m / s or more;

Freight paving;

Ship;

Special purpose;

For work in buildings and premises related to categories A and B * in the explosion and fire hazard;

To work in premises with aggressive pairs or gas gases;

To work in conditions of moisture condensation in a mine or machine room, loss of inlet or ice formation on equipment.

* Categories of buildings and premises in the explosion and fire hazard are determined at the design stages of buildings and structures in accordance with the requirements of national fire hazard.

The requirements of this standard are mandatory.

Mandatory requirements for the quality of elevators that ensure their safety for the life, health and property of the population, environmental protection are set out in the section.

2 Regulatory references

This standard uses references to the following standards and state supervision documents:

The main parameters and dimensions of electrical freight elevators - according to GOST 8823.

The main parameters and the size of electrical cargo small elevators - according to GOST 8824.

The experimental elevator designation is given in the application.

4 Technical requirements

4.1 Characteristics

4.1.2 Installation of elevators for work in buildings and premises related to the explosion and fire hazard to category B should be carried out in accordance with the requirements of national building standards and rules for elevators of this category.

4.1.3 Installation of elevators in buildings and structures located in areas with the intensity of seismic exposure 7-9 points is allowed when performing requirements that take into account the conditions of operation specified in the regulatory or design documentation.

4.1.4 The values \u200b\u200bof elevator indicators must correspond to the tables and.

4.1.5 Elevators should work in the operational modes specified in the table, and maintain a working condition at the height above sea level up to 2000 m.

When operating the elevator at height above sea level from 1000 to 2000 m, the number of inclusions per hour is reduced by 1% each 100 m.

4.1.6 Elevators are manufactured to work from an AC network with a frequency of 50 Hz and a voltage of 380 V.

Table 1

Passenger elevators

for residential buildings

for public buildings and buildings of industrial enterprises

for industrial buildings

hospital

Nominal speed, m / s

0,71

0,71

Assigned service life, years

Stop accuracy of elevator cabins, mm, driven:

Adjustable

± 10.

Unregulated

± 35.

BUT, no more

Sound level in the cockpit when opening and closing doors, dB BUT,no more

Vibrating the floor of the cab floor with the steady movement, m / s, not more

0,06 10 -2

Corrected sound power level winch, dB BUT, not less

Load capacity, kg.

320;

800; 1000; 1250; 1600

Note - At the end of the appointed service life, the elevator is carried out by a survey in accordance with the procedure established by Gosgortkhnadzor.

Table 2

Freight elevators

normal

small

Nominal speed, m / s

0,25*; 0,5

0,25**; 0,4

0,4; 0,5

Average work on failure, h, not less

Assigned service life, years

Sound level in the cockpit when installed movement, dB BUT, no more

Vibration, m / s, no more

0.32 · 10 -2

0.16 · 10 -2

0.16 · 10 -2

Corrected sound power level winch, dB BUT, no more

Load capacity, kg.

1000

1600

2000 or more

* For elevators with a carrying capacity of 5000 kg.

** For elevators with a carrying capacity of 4000 and 6300 kg.

Note - At the end of the appointed service life, the elevator conducts it to be examined in accordance with the procedure established by the Gosgortkhnadzor.

Table 3.

Nominal speed, m / s

Operating mode

A type

View

Number of inclusions per hour, no more

Relative duration of the inclusion of PV,%, not more

Passenger

for residential buildings

0,4 - 0,71

1,0-1,6

180*

for buildings of public and industrial enterprises

1,0; 1,6

180; 200*

hospital

180*

180; 200*

for industrial buildings

0,4 - 0,71

Cargo

normal

0,25

0,4; 0,5

released, with Monorail

0,4; 0,5

Cargo small

0,4; 0,5

* For elevators with a carrying capacity of St. 630 kg

Table 4.

Type of climatic execution

Limit operating temperatures, ° С

Top value of relative humidity

A type

View

shakhty

machine room

Passenger

for residential buildings, public and industrial enterprises, hospital

Uhl

From +40 to +1

"+40" +5

80% at + 25 ° С

80% "+ 25 ° С

From +55 to +1

"+55" +5

98% at + 35 ° С

98% "+ 35 ° С

for industrial buildings

Uhl

From +40 to -40

"+40" +5

98 % at + 25 ° С

80% "+ 25 ° С

Cargo

normal, extrusive, with monorail

Uhl

From +40 to -20

"+40" +5

98% at + 25 ° С

98% "+ 25 ° С

T, O.

From +45 to -10

"+45" +5

98% at + 35 ° С

98% "+ 35 ° С

Cargo small

Uhl

From +40 to +1

"+40" +5

80% at + 25 ° С

80% "+ 25 ° С

* When recording the climatic performance of the elevator, the category of its placement indicates the category of engine room location.

At the request of the customer, elevators can be made to work on the AC mains:

50 Hz frequency with voltage 240 and 415 V;

The frequency of 60 Hz " 220; 230; 380; 400; 415 and 440 V.

The elevators should be operational when they are connected to the AC network with deviations from their nominal current frequency values \u200b\u200bof no more than 1% and voltage no more than 10%.

4.1.7 Radioomies arising from the function of the elevator should not exceed the values \u200b\u200bestablished by GOST 23511 and the national norms of admitted industrial radio interference. The tension of the radiopomech field created by the elevator is not normalized.

4.1.8 Elevators, depending on the operating conditions, the climatic execution and placement categories should be made (according to GOST 15150) shown in the table.

4.1.9 Cabs of freight elevators with solid doors, except for elevators with external control, as well as cabins of passenger elevators for residential and public buildings and buildings of industrial enterprises should have natural ventilation.

Cabins of passenger, hospital and freight elevators (with conductor) with solid doors in tropical versions should have natural and forced ventilation.

4.1.9.1 Passenger elevators with automatic doors with a speed of 1.0 m / s and more should have a fire danger mode, which is included in the signal on the signal from the automatic fire alarm systems and providing, regardless of loading and directions of the cabin, return Its on the main planting area, opening and holding in the open position of the doors of the cabin and mines.

4.1.9.2 Passenger elevators intended to transport fire units should have the operation of "transportation of fire divisions". The transfer of the elevator control to this mode should be carried out from the cab, while the control system should provide the elevator only on the clause orders.

4.1.10 Facing the cabin of the cabin, plafoons, flooring, as well as the buttons of orders and call posts, should be made from non-combustible or hard-scale materials.

4.1.11 In the roof of the cabin of the elevator used to transport fire units, the hatch should be provided with a size of at least 700x500 mm. Luke must be equipped with a switch controlling its locking.

4.1.12 The doors of the elevator mine must be fire-based second-type and meet the requirements of SNiP 21-01 (sections 3 and 4).

Fire resistance limit of the passenger elevator shaft for residential buildings at a speed of up to 1.0 m / s. Not installed.

The doors of the cargo elevator shaft are allowed not to equip the device for self-blocking.

Cargo small elevators with two stops is allowed to be executed in a metal frame mine with a fencing of metal sheets. At the same time, fire-prevention requirements for shaft doors are not presented.

4.1.13. The electrical drive system and the elevator automation should provide the ability to connect external elevator operation systems and establishing its faults.

Requirements for devices and alarm elevator - according to GOST 28911. When installing a group of two and more passenger elevators having the same rated speed and, as a rule, the number of stops must be applied to the group control system with a common control device for control on each planting area.

4.1.14 Signal colors and safety signs - according to GOST 12.4.026 and GOST 28911, respectively.

Wherein:

The surfaces of the oil, caps, drain plugs, oil supplies should have a red coating;

The surface of the rotation parts, not closed with a cover, except for the surfaces of the rotation parts on the tensioning device of the speed limiter and counterweight, should have a yellow coating.

It is allowed to paint the end surfaces of the rotation parts in the form of an annular strip of a width of at least 20 mm in accordance with the place of color in the drawings.

Passenger elevators that have the work of "Transportation of fire units" should have a distinctive symbolism located on the main seating area, in accordance with the instructions of the design documentation.

4.1.15 Technical documentation for the elevator must comply with the requirements of the elevator design project, approved in the prescribed manner.

4.1.16 Painted surface coatings of elevator equipment must match the coverage classes specified in the table.

Table 5.

Class coating inGOST 9.032.

The surface of the components of the elevator, located in a mine, machine and block room, including:

External surfaces of the fence cabins (shields);

Non-sash cabinets of cabin doors and mines;

Guides and counterweights, except for the working surface of the head of the guide profile;

Details (except fastening) and assembly units of fastening of guide cabins and counterweight;

Cabs and counterweight frame surfaces, shunt brackets and sensors in the mine and on the cabin, metal structures of blocks, buffers, tensioning devices, transformers and other electrical equipment, frame and subframes winch;

Unprocessed surfaces of blocks and pulleys, grounding tires;

Cast iron cargoes of counterweight and tensioning rope device, speed limiter

The inner surfaces of the cabin of passenger elevators, not visible from the inside of it. The inner surface of the cab of the cargo elevators visible from the inside.

Unprocessed gear surfaces, steering wheel, winch brakes, speed limiter, hydraulic buffer

The inner surface of the passenger elevator cabin visible from the inside of it.

The front surfaces of the doors of the cabin and shaft, if they do not have another decorative finish

IV, III (at the request of the customer)

Metal coatings must correspond to GOST 9.301. The painting of equipment for elevators of tropical climatic execution - according to GOST 9.401.

4.1.17 The equipment of the freight elevator in agreement with the customer is allowed to cover the primer with the subsequent color after the installation.

It is allowed no color in hard-to-reach places.

Inaccessible places should be indicated in the design documentation.

Cast iron of the counterweight and the stretch device of the elevator speed limiter is allowed not to cover.

4.1.18 The front side of the mine door sashs of one or more elevators should have on each stopping platform the coating of one color and one shade, if there is no other customer requirement.

4.1.19 Welding Places (Welded Sews and Oil Surfaces), made when installing the elevator, should be protected by the coating provided for them in the technical documentation for the elevator.

4.1.20 The ropes must be a dimensional length of one bay and with a purified surface. Dirt and other inclusions on the surface of the ropes are not allowed.

The ends of the ropes should be protected from spinning, and the sections of the cut is made in accordance with 2.1.9 GOST 3241.

4.1.21 Suspended electrical elevator cable must be broken, with closer and installed wires.

Wires of wiring harnesses, laid in the mine and machine room, must be marked. In coordination with the customer, the delivery of measuring length wires is allowed.

4.2 Completeness

4.2.1 The elevator must include:

Elevator equipment in accordance with the specification on the elevator, incl. Spare parts and materials designed for the warranty period of the elevator, tools and accessories (zip) required for the maintenance and repair of the elevator; Spare products for commissioning work during installation (winters) in accordance with their Vedomosti;

Technical documentation sent with elevator and list of parts for replacement in accordance with applications and, accordingly.

In the case of sending several elevators of one type, type, load capacity, speed and execution (various arrangements of the counterweight, passing or non-passing cabin, etc.) for installation on one object or building, the technical documentation is sent in one instance by 5 elevators. Passport, conceptual electrical circuit, electrical connections, mounting (installation) drawing should be sent with each elevator.

4.2.2 Composite parts of the elevator: winch, cab, Mine doors, hydraulic buffer, speed limiter, the tensioning device should be sent in the assembled and adjusted form if there is no other customer requirement.

Brackets of fastening of storey switches, shunts, selection sensors, storey terminal boxes should be sent with attached clamps. Details of the fastening of the guides should be sent in the assembled form with attached clamps.

4.2.3 In disassembled form, it is allowed to send:

Counterweight;

Cabin of a cargo elevator with dimensions in terms of 1500x2000 mm and more;

Cabin of the hospital elevator for buildings of medical and prophylactic institutions;

Doors of the cargo elevators with width of the opening of more than 2000 mm or a height of more than 2600 mm;

Framing (with its own) openings of passenger elevators.

4.3 Marking

4.3.1 Each elevator must be equipped with a signboard made according to GOST 12969, GOST 12970 and GOST 12971.

The elevator plate should indicate:

Name or trademark of the elevator manufacturer;

Lifting equipment marking for the regions of the Far North of the Russian Federation and hard-to-reach areas (for example, mountain, etc.) - according to GOST 15846.

4.4 Packaging

4.4.1 Composite parts of the elevator equipment before packaging must be canned.

Temporary anti-corrosion protection - according to GOST 9.014.

The use of conservation oils for conservation of ropes is not allowed. Their use is allowed to cover the surface of the guide tagging profile.

The preservation of components of elevator equipment should ensure their protection to the first subcast: component parts of the elevator - up to one year, spare parts - up to 2.5 years. The renouncer should hold the elevator owner.

The packaging sheets should indicate: the date and period of the reconstruction, as well as means of temporary corrosion protection.

4.4.2 Preservation and packaging of wires and cables should be carried out with regard to the requirements of GOST 18690, electrical equipment (including bundles) - according to GOST 23216.

4.4.3 Packaging of equipment and technical documentation of the elevator - according to GOST 23170.

The ropes are packaged into a polymer film according to GOST 10354 or on another NTD, coordinated with the GOSGORTECHNADOR, or in waterproof paper according to GOST 8828 and GOST 515.

The rope shown in the bay must be tightly tied up with a soft wire (according to GOST 3282 or other NTD) or a strand of the same rope, or a tape according to GOST 3560 (or other NTD) at least four places that are evenly located around the circle.

4.4.4 Packaging Equipment Equipment in tropical climatic execution must comply with the requirements of GOST 24634, while Tara timber must be impregnated with antiseptic. It is allowed instead of the antiseptation of paint boxes in two layers of the gray paint of the PF-115 brand according to GOST 6465 or other similar paints.

4.4.5 Packaging Equipment Equipment sent to the regions of the Far North of the Russian Federation and hard-to-reach areas - according to GOST 15846.

5 Safety requirements

The safety of elevators is ensured by the implementation of the set of requirements - (except -,), sections, -, of this standard and Pubel Gosgortkhnadzor.

6 Rules acceptance

6.1 Composite parts (equipment) of the elevator (including Zip and Wali) should be subjected to acceptance control by the manufacturer's technical control service in order to determine their suitability for sending to the consumer.

6.2 Remote control of the components of the elevator should be statistical alternatively according to GOST 18242.

Parameters, dimensions, requirements to be controlled, sampling and types of defects should be indicated in the technical documentation for the elevator.

a) control plan:

Control level - II,

Type of control plan - single-stage,

b) acceptance level of winch defective, gearbox (if it is produced as a spare part), elevator doors drive, speed limit, catcher, hydraulic buffer, cab loading devices, shaft doors, cabin doors, springs of responsible destination (buffer springs, brakes, trappers , cab pendants and counterweight, etc.), zip and winters:

2.5% - for significant defects;

6.5%-for insignificant defects.

Acceptance level of defectiveness of other assembly units and equipment parts:

0% - for critical defects;

6.5% - for significant defects.

Production cycle with continuous statistical control - one year.

6.4 Purchased products, materials and raw materials should be subjected to input control according to GOST 24297.

When input control, the low-voltage complete device (HCC) must be checked for operation.

Upon admission from the Customer or consumer elevators of advertising or claims to the quality of the purchase product, the elevator manufacturer during input control should use another more stringent type of control according to GOST 18242.

6.5 Composite parts of the elevator, details and castings produced by other manufacturers should be subjected to an elevator manufacturer to visual control to detect possible damage to this equipment during transportation.

Manufacturer of equipment, details and castings upon receipt of claims from the elevator manufacturer must for 3 days to inform it about the decision to eliminate the defect.

6.6 Acceptance tests of component parts (equipment) elevator

The components of the elevator mentioned in should be subjected to acceptance tests by its manufacturer on programs and methods approved in the prescribed manner.

The size of the sample of the samples of the components of the elevator is set by the elevator manufacturer and is indicated in the technical documentation.

After making a prototype:

Preliminary;

Acceptable;

When developing production - qualifying;

With serial production:

Acceptance tests of component parts of the elevator;

Periodic;

Typical.

6.8 The frequency of testing of the elevator indicated in, the number of elevators to be subjected to these tests, and the number of elevators in the batch, from which the test elevator is selected, must match the table.

6.9 Periodic Tests

6.9.1 Periodic elevator tests are carried out in order to verify the stability of the quality of manufacturing and the possibility of continuing its release.

Periodic tests should include verification of all mandatory requirements established by this standard and Pubel Gosgorekhnadzor.

6.9.2 In case of unsatisfactory results of periodic tests, at least one of the items of the program, repeated tests should be carried out on these points on a twin number of the corresponding components of the elevator taken from the same batch. Results of repeated tests are final.

Table 6.

Test frequency

Number of elevators

The number of elevators in the party, from which the elevators are taken for testing

Preliminary

One-time - after the manufacture of prototypes

All experimental elevator samples, the number of which is determined by the technical assignment to the development

Remote

Also

All experienced samples that have passed preliminary tests.

Qualification

When setting the elevator production of this model

At least 3.

Periodic

At least once every three years

At least 7 *

Typical

Every time the design change

At least 3.

* When conducting tests, the manufacturer of the elevators is selected from among the past acceptance control and ready to send to the consumer. When conducting tests on the object of operation, taken from the number made by no more than 18 months before the test.

7 Monitoring methods

7.1 Measurement Requirements

7.1.1 Measurement tools must be believed in accordance with the requirements of GOST 8.002 and GOST 8.513.

Testing equipment must be certified according to GOST 24555, non-standardized measurement tools must undergo metrological certification according to GOST 8.326.

7.2 Preparation for Testing

7.2.1 Before carrying out acceptance and qualification tests of the elevator, tests for the reliability of the winch, drive doors, cabin doors, shaft doors, speed limit, trappers, hydraulic buffers, booth loading devices.

It is allowed not to test the reliability of the equipment borrowed from other elevators, provided that it has been tested earlier and on it, the manufacturer has an rationale for maintaining reliability indicators under operating conditions.

The low-voltage complete device must have a document confirming its reliability.

7.2.2 Prior to periodic tests, the manufacturer must submit materials confirming the reliability indicators of elevators.

Confirmation of reliability indicators is carried out on the basis of a test for the reliability of the elevator or its component parts (equipment) in the period between periodic tests or by the results of operational observations of the work of similar elevators.

Methods and plans for reliability and observations during operation - according to GOST 27.410.

7.2.3 For typical elevator tests, which uses equipment with changes that can affect the technical characteristics of the elevator and / or operation, the tests of each modified equipment should be carried out.

With positive results of testing modified equipment, typical elevator tests are allowed.

7.3 Elevator testing

7.3.1 The tests of elevators should be carried out in accordance with the programs and methods of tests, coordinated in the prescribed manner.

7.3.1.1 Before the start of the elevator test, the manufacturer must have a "act of technical readiness of the elevator".

Tests should be carried out on the territory of the manufacturer of elevators. The test of the elevator at the operating facility should be coordinated with the Gosgortkhnadzor.

It is not allowed to replace the elevator tests by testing its layout.

When testing group control of elevators at three or more elevators, this system is allowed in the group.

When testing several elevators of the same type and type, it is allowed to determine the quantitative and qualitative characteristics of a single elevator - a typical representative of the group (determined by the elevator developer). The remaining elevators of the group should be checked characteristics that differ from the characteristics of a typical representative.

With unsatisfactory test results for one or more indicators, the resumption of repeated tests is allowed only after establishing the causes of deficiencies and eliminate them.

8 Transportation and storage

8.1 Transportation of equipment equipment is allowed to carry out any kind of transport in accordance with the rules operating on them.

When transporting elevator equipment on the decks of ships, the elevator manufacturer must take into account the impact of the type III atmosphere according to GOST 15150

Transportation period, month, no more

Uhl, t, about

It is allowed to store elevator equipment under storage conditions 8 according to GOST 15150, both at the manufacturer and the customer for 3 months, with a total storage period of not more than 6 months.

9 Installation and Operation Inspection

9.1 Installation of elevators should be carried out in accordance with the requirements of GOST 22845, Pubel Gosgortkhnadzor and technical documentation for the installation of the elevator.

9.2 The exploitation of elevators should be carried out in accordance with the requirements of Pubel Gosgortkhnadzor and operating instructions.

10 Warranties manufacturer

The manufacturer guarantees the elevator compliance (in general, including composite parts and components) with the requirements of this standard, subject to compliance with the requirements for operation, storage, transportation and installation.

Warranty period - 18 months from the date of signing the "Act of an elevator acceptance".

Appendix A.

Schemes for constructing the conditional designation of electric passenger, cargo and small freight elevators

1 scheme of conditional designation of passenger elevators

1 - type of elevator; LP - passenger elevator with basic parameters and constructive performance according to GOST 5746;

2 - a group of conditional designation of the basic parameters of the elevator (carrying capacity and rated speed), installed in accordance with the methodology operating in the lift construction of the CIS countries;

3 - An indication of the installation of an elevator - single (in the case notation does not indicate), group (g) from group 2 - 4, 6 elevators (g2 - g4, g6);

4 - the number of elevator stops;

5 -

6 -

7 - indication of the presence of a modulation of the elevator "Transportation of fire units" (P);

8 -

Example of the conditional notationpassenger elevator for residential buildings with basic sizes and structural versions according to GOST 5746, with a carrying capacity of 400 kg, with a rated speed of 0.71 m / s, single installation, with a number of stops 10, performed for operation in the zone of moderately cold climate, placement categories 4 and in the area with the intensity of the seismic effects of 8 points that does not have a mode of operation "Transportation of fire units":

LP 0471 10 UHL4 C8 GOST 22011-95

2 scheme of conditional designation of freight elevators

1 - type and type of elevator with parameters, primary sizes and constructive design according to GOST 8823:

Lift cargo regular (lgo);

Freight release elevator (LGV);

Freight elevator usual with monorail (LGOM);

2 - the sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - indication of the gauze of the cabin in terms of the elevator of this carrying capacity - the first (smaller - in the conditional designation does not indicate) or the second (greater) (b);

8 - view of the cab - the passage (Ave.), non-volume (neop.);

9 - climatic performance and category of elevator placement;

10 - An indication of the execution of the elevator (the execution without taking into account the seismic effects in the conditional designation does not indicate), which takes into account the seismic impact (C) with the intensity of 7 - 9 points (C7 - C9);

11 - Designation of this Standard.

Example of the conditional notation a cargo conventional elevator with basic sizes and structural versions according to GOST 8823, with a sequence registration number 922, with a carrying capacity of 1000 kg, at a rated speed of 0.4 m / s, a lifting height of 60 m, with a number of stops 16, from the passage of the second dimension, for Operation in the zone of moderately cold climate and placement category 4:

LGO 922 1000 x 0.4 60 16 B PR Uhl4 GOST 22011-95

3 scheme of the conditional designation of cargo small elevators

1 - type of elevator; LGM - freight elevator small with parameters, basic sizes and constructive design according to GOST 8824;

2 - sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - view of the cab - Through (SLE.), Non-cut (narrow);

8 - climatic performance and category of elevator placement;

9 - Designation of this Standard.

Example of the conditional notation a cargo small elevator with parameters, basic sizes and constructive design according to GOST 8824, with a registration number of model 958, a carrying capacity of 100 kg, at a rated speed of 0.4 m / s, a rise in 45 m high, with a number of stops 14, with a non-separated cabin, in Execution for operation in the zone of moderately cold climate and with the category of placement 4:

LGM 958 100 x 0.4 45 NG UHL4 GOST 22011-95

Appendix B.

(mandatory)

List of a set of technical documentation *

* Depending on the type and type of specific elevator, the list of documents for its equipment is specified by the developer.

The technical documentation of the elevator includes the following documents:

Elevator Passport according to Pubel Gosgortecadzor with documents certifying quality: winches, speed limit, doors drive, hydraulic buffer, springs of cabins and counterweight, brake springs, trap springs. NCU passport (stored with the elevator passport);

Mounting drawing (installation drawing, the sample of which is agreed with the Gosgortkhnadzor) (2 copies);

Installation instructions, start-up, regulation and running;

Technical description and instruction manual;

A conceptual electrical circuit with a list of elements (3 copies);

Description of the electric drive and automation (allowed to be supplied as part of a technical description and instruction manual);

Electrical diagram of the electrical components of the elevator control (comes with the NCU);

Electrical diagram of elevator compounds;

Vedomosti Zip and winters;

Drawings of parts for replacement (see application);

Assembly drawings (and specification) Elevator equipment for: speed limiter, hydraulic buffer, winch, gearbox, brake, coupling, tap block, cabin, catcher, automatic door drive, minor door, automatic and manual shaft door locks, wire wiring Machine room, shaft and cabin, counterweight.

Appendix B.

List of parts for replacement *

* The parts indicated in the list are designed to replace failed (wear, breakage) during the period of the elevator after the expiration of its warranty period

Pulleys canned.

Brake block assembly.

Spring brakes.

Cabin sliding shoe liner.

Roller (rollers) Cabin shoe.

Insert of the sliding door of the cab of freight elevators.

Passenger lifts shoe shoes.

Roller of the door of the cabin of freight elevators.

Passenger lift carriage carriage roller.

The roller drove the drive of the doors of passenger elevators.

Rubber stop drive doors.

The liner of the sliding shoe counterweight.

Roller carriages of automatic sliding doors of the mine.

Roller Ogrushed Mine Door Castle.

Pulley speed limiter.

Block of tap traction ropes of elevators.

Cleaves of clinorem transmission of cabin drives.

Ring Rubber Cabin Mobile Field Loading Device.

Cabin door drive belt.

Note - The list of parts is specified for a particular elevator by its developer.

Keywords: passenger, cargo and cargo lifts Small elevators, technical requirements, safety requirements, acceptance rules, transportation and storage

    Appendix A (recommended). Schemes for constructing the conventional designation of electric passenger, cargo and small freight elevators Appendix B (mandatory). List of a set of technical documentation Appendix B (recommended). List of parts for replacement

Interstate Standard GOST 22011-95
"Passenger and freight elevators. Technical conditions"
(put into effect by the Resolution of the State Standard of the Russian Federation of February 15, 1996 N 68)

With changes and additions from:

Passenger and Goods Lifts. Specifications.

6.9. Periodic tests

6.9.1. Periodic elevator tests are carried out in order to verify the stability of the quality of manufacture and the possibility of continuing its release.

Periodic tests should include verification of all mandatory requirements established by this standard and Pubel Gosgorekhnadzor.

6.9.2. With unsatisfactory results of periodic tests, at least one of the items of the program should be repeated tests on these points on a twin number of the corresponding components of the elevator taken from the same batch. Results of repeated tests are final.

Table 6.

Type of test Periodicity
test
number
lifts.
Number of elevators
in the party, from
which is selected
elevators for
test
Preliminary One-time - after
manufacturing
experimental samples
All experienced elevator samples,
the number of which is defined
technical task on
development
Remote Also 1 All experienced
samples past
preliminary
test
Qualification When setting
lift production
this model
1 At least 3.
Periodic No less than once
in 3 years
1 At least 7.
Typical At each
change
designs
1 At least 3.
* When conducting tests, the manufacturer of the elevator is taken from among
past acceptance controls and ready to send to the consumer. For
tests on the object of operation are taken from among
manufactured not more than 18 months before the test

7. Monitoring methods

7.1. Measurement Requirements

7.1.1. Measurement tools must be believed in accordance with the requirements of GOST 8.002 and GOST 8.513.

Testing equipment must be certified according to GOST 24555, non-standardized measurement tools must undergo metrological certification according to GOST 8.326.

7.2. Preparation for testing

7.2.1. Prior to the admission and qualification tests of the elevator, tests for the reliability of the winch, door drive, cabin doors, shaft doors, speed limiter, trappers, hydraulic buffers, booth loading devices are performed.

It is allowed not to test the reliability of the equipment borrowed from other elevators, provided that it has been tested earlier and on it, the manufacturer has an rationale for maintaining reliability indicators under operating conditions.

The low-voltage complete device must have a document confirming its reliability.

7.2.2. Prior to periodic tests, the manufacturer must submit materials confirming the reliability of elevators.

Confirmation of reliability indicators is carried out on the basis of a test for the reliability of the elevator or its component parts (equipment) in the period between periodic tests or by the results of operational observations of the work of similar elevators.

Methods and plans for reliability and observations during operation - according to GOST 27.410.

7.2.3. To carry out typical elevator tests, which uses equipment with changes that can affect the technical characteristics of the elevator and / or operation, the tests of each modified equipment must be carried out.

With positive results of testing modified equipment, typical elevator tests are allowed.

7.3. Conducting elevator testing

7.3.1. The tests of elevators should be carried out in accordance with the programs and methods of tests, coordinated in the prescribed manner.

7.3.1.1. Prior to the start of the elevator test, the manufacturer must have a "act of technical readiness of the elevator".

Tests should be carried out on the territory of the manufacturer of elevators. The test of the elevator at the operating facility should be coordinated with the Gosgortkhnadzor.

It is not allowed to replace the elevator tests by testing its layout.

When testing group control of elevators at three or more elevators, this system is allowed in the group.

When testing several elevators of the same type and type, it is allowed to determine the quantitative and qualitative characteristics of a single elevator - a typical representative of the group (determined by the elevator developer). The remaining elevators of the group should be checked characteristics that differ from the characteristics of a typical representative.

With unsatisfactory test results for one or more indicators, the resumption of repeated tests is allowed only after establishing the causes of deficiencies and eliminate them.

8. Transportation and storage

8.1. Transportation of elevator equipment is allowed to carry out any type of transport in accordance with the transportation rules operating on them.

GOST 15150 right now or request Hot line in system.

GOST 22011-95

Interstate standard

Passenger elevators
And freight

Technical conditions

Interstate Council
BY
Minsk

Preface

1 Developed by TC 209 "Elevators and Building Lifts"

Submitted by the State Standard of Russia

2 Adopted by the Interstate Council for Standardization, Metrology and Certification (Protocol No. 8-95 of October 12, 1995)

Name of state

Name of the National Standardization Authority

The Republic of Azerbaijan

Azgosstandard

Republic of Belarus

Belstandard.

The Republic of Kazakhstan

Gosstandart of the Republic of Kazakhstan

Kyrgyz Republic

Kyrgyzstandard

The Republic of Moldova

Moldova Standard

the Russian Federation

State Standard of Russia

The Republic of Tajikistan

Tajik State Center for Standardization, Metrology and Certification

Turkmenistan

Home State Inspectorate of Turkmenistan

The Republic of Uzbekistan

UZGOSSTANDART

State Standard of Ukraine

3 Resolution of the Committee of the Russian Federation on Standardization, Metrology and Certification of February 15, 1996 No. 68 Interstate Standard 22011-95 was enacted directly as the State Standard of the Russian Federation from January 1, 1997.

4 instead of GOST 22011-90

5 reprint

GOST 22011-95

Interstate standard

Passenger and freight elevators

Technical conditions

Passenger and Goods Lifts. Specifications.

Date of introduction 1997-01-01

1 AREA OF USE

This standard applies to electric passenger, hospital, cargo and cargo small elevators (hereinafter - elevators).

Standard does not apply to elevators:

Passenger at rated speed (hereinafter referred to as speed) 2.0 m / s or more;

Freight paving;

Ship;

Special purpose;

For work in buildings and premises related to categories A and B * in the explosion and fire hazard;

To work in premises with aggressive pairs or gas gases;

To work in conditions of moisture condensation in a mine or machine room, loss of inlet or ice formation on equipment.

* Categories of buildings and premises in the explosion and fire hazard are determined at the design stages of buildings and structures in accordance with the requirements of national fire hazard.

The requirements of this standard are mandatory.

Mandatory requirements for the quality of elevators that ensure their safety for the life, health and property of the population, environmental protection are set out in the section.

2 Regulatory references

This standard uses references to the following standards and state supervision documents:

The main parameters and dimensions of electrical freight elevators - according to GOST 8823.

The main parameters and the size of electrical cargo small elevators - according to GOST 8824.

The experimental elevator designation is given in the application.

4 Technical requirements

4.1 Characteristics

4.1.2 Installation of elevators for work in buildings and premises related to the explosion and fire hazard to category B should be carried out in accordance with the requirements of national building standards and rules for elevators of this category.

4.1.3 Installation of elevators in buildings and structures located in areas with the intensity of seismic exposure 7-9 points is allowed when performing requirements that take into account the conditions of operation specified in the regulatory or design documentation.

4.1.4 The values \u200b\u200bof elevator indicators must correspond to the tables and.

4.1.5 Elevators should work in the operational modes specified in the table, and maintain a working condition at the height above sea level up to 2000 m.

When operating the elevator at height above sea level from 1000 to 2000 m, the number of inclusions per hour is reduced by 1% each 100 m.

4.1.6 Elevators are manufactured to work from an AC network with a frequency of 50 Hz and a voltage of 380 V.

Table 1

Passenger elevators

for residential buildings

for public buildings and buildings of industrial enterprises

for industrial buildings

hospital

Nominal speed, m / s

Assigned service life, years

Stop accuracy of elevator cabins, mm, driven:

Adjustable

Unregulated

BUT, no more

Sound level in the cockpit when opening and closing doors, dB BUT,no more

Vibrating the floor of the cab floor with the steady movement, m / s, not more

Corrected sound power level winch, dB BUT, not less

Load capacity, kg.

800; 1000; 1250; 1600

Note - At the end of the appointed service life, the elevator conducts it to be examined in accordance with the procedure established by the Gosgortkhnadzor.

Table 2

Freight elevators

Nominal speed, m / s

Average work on failure, h, not less

Assigned service life, years

Sound level in the cockpit when installed movement, dB BUT, no more

Vibration, m / s, no more

Corrected sound power level winch, dB BUT, no more

Load capacity, kg.

2000 or more

* For elevators with a carrying capacity of 5000 kg.

** For elevators with a carrying capacity of 4000 and 6300 kg.

Note - At the end of the appointed service life, the elevator conducts it to be examined in accordance with the procedure established by the Gosgortkhnadzor.

Table 3.

Nominal speed, m / s

Operating mode

Number of inclusions per hour, no more

Relative duration of the inclusion of PV,%, not more

Passenger

for residential buildings

for buildings of public and industrial enterprises

hospital

for industrial buildings

Cargo

released, with Monorail

Cargo small

* For elevators with a carrying capacity of St. 630 kg

Table 4.

Type of climatic execution

Limit operating temperatures, ° С

Top value of relative humidity

machine room

Passenger

for residential buildings, public and industrial enterprises, hospital

From +40 to +1

80% at + 25 ° С

80% "+ 25 ° С

From +55 to +1

98% at + 35 ° С

98% "+ 35 ° С

for industrial buildings

From +40 to -40

98 % at + 25 ° С

80% "+ 25 ° С

Cargo

normal, extrusive, with monorail

From +40 to -20

98% at + 25 ° С

98% "+ 25 ° С

From +45 to -10

98% at + 35 ° С

98% "+ 35 ° С

Cargo small

From +40 to +1

80% at + 25 ° С

* When recording the climatic performance of the elevator, the category of its placement indicates the category of engine room location.

At the request of the customer, elevators can be made to work on the AC mains:

50 Hz frequency with voltage 240 and 415 V;

The frequency of 60 Hz "220; 230; 380; 400; 415 and 440 V.

The elevators should be operational when they are connected to the AC network with deviations from their nominal current frequency values \u200b\u200bof no more than 1% and voltage no more than 10%.

4.1.7 Radioomies arising from the function of the elevator should not exceed the values \u200b\u200bestablished by GOST 23511 and the national norms of admitted industrial radio interference. The tension of the radiopomech field created by the elevator is not normalized.

4.1.8 Elevators, depending on the operating conditions, the climatic execution and placement categories should be made (according to GOST 15150) shown in the table.

4.1.9 Cabs of freight elevators with solid doors, except for elevators with external control, as well as cabins of passenger elevators for residential and public buildings and buildings of industrial enterprises should have natural ventilation.

Cabins of passenger, hospital and freight elevators (with conductor) with solid doors in tropical versions should have natural and forced ventilation.

4.1.9.1 Passenger elevators with automatic doors with a speed of 1.0 m / s and more should have a fire danger mode, which is included in the signal on the signal from the automatic fire alarm systems and providing, regardless of loading and directions of the cabin, return Its on the main planting area, opening and holding in the open position of the doors of the cabin and mines.

4.1.9.2 Passenger elevators intended to transport fire units should have the operation of "transportation of fire divisions". The transfer of the elevator control to this mode should be carried out from the cab, while the control system should provide the elevator only on the clause orders.

4.1.10 Facing the cabin of the cabin, plafoons, flooring, as well as the buttons of orders and call posts, should be made from non-combustible or hard-scale materials.

4.1.11 In the roof of the cabin of the elevator used to transport fire units, the hatch should be provided with a size of at least 700x500 mm. Luke must be equipped with a switch controlling its locking.

4.1.12 The doors of the elevator mine must be fire-based second-type and meet the requirements of SNiP 21-01 (sections 3 and 4).

Fire resistance limit of the passenger elevator shaft for residential buildings at a speed of up to 1.0 m / s. Not installed.

The doors of the cargo elevator shaft are allowed not to equip the device for self-blocking.

Cargo small elevators with two stops is allowed to be executed in a metal frame mine with a fencing of metal sheets. At the same time, fire-prevention requirements for shaft doors are not presented.

4.1.13. The electrical drive system and the elevator automation should provide the ability to connect external elevator operation systems and establishing its faults.

Requirements for devices and alarm elevator - according to GOST 28911. When installing a group of two and more passenger elevators having the same rated speed and, as a rule, the number of stops must be applied to the group control system with a common control device for control on each planting area.

4.1.14 Signal colors and safety signs - according to GOST 12.4.026 and GOST 28911, respectively.

Wherein:

The surfaces of the oil, caps, drain plugs, oil supplies should have a red coating;

The surface of the rotation parts, not closed with a cover, except for the surfaces of the rotation parts on the tensioning device of the speed limiter and counterweight, should have a yellow coating.

It is allowed to paint the end surfaces of the rotation parts in the form of an annular strip of a width of at least 20 mm in accordance with the place of color in the drawings.

Passenger elevators that have the work of "Transportation of fire units" should have a distinctive symbolism located on the main seating area, in accordance with the instructions of the design documentation.

4.1.15 Technical documentation for the elevator must comply with the requirements of the elevator design project, approved in the prescribed manner.

4.1.16 Painted surface coatings of elevator equipment must match the coverage classes specified in the table.

Table 5.

The surface of the components of the elevator, located in a mine, machine and block room, including:

External surfaces of the fence cabins (shields);

Non-sash cabinets of cabin doors and mines;

Guides and counterweights, except for the working surface of the head of the guide profile;

Details (except fastening) and assembly units of fastening of guide cabins and counterweight;

Cabs and counterweight frame surfaces, shunt brackets and sensors in the mine and on the cabin, metal structures of blocks, buffers, tensioning devices, transformers and other electrical equipment, frame and subframes winch;

Unprocessed surfaces of blocks and pulleys, grounding tires;

Cast iron cargoes of counterweight and tensioning rope device, speed limiter

The inner surfaces of the cabin of passenger elevators, not visible from the inside of it. The inner surface of the cab of the cargo elevators visible from the inside.

Unprocessed gear surfaces, steering wheel, winch brakes, speed limiter, hydraulic buffer

The inner surface of the passenger elevator cabin visible from the inside of it.

The front surfaces of the doors of the cabin and shaft, if they do not have another decorative finish

IV, III (at the request of the customer)

Metal coatings must correspond to GOST 9.301. The painting of equipment for elevators of tropical climatic execution - according to GOST 9.401.

4.1.17 The equipment of the freight elevator in agreement with the customer is allowed to cover the primer with the subsequent color after the installation.

It is allowed no color in hard-to-reach places.

Inaccessible places should be indicated in the design documentation.

Cast iron of the counterweight and the stretch device of the elevator speed limiter is allowed not to cover.

4.1.18 The front side of the mine door sashs of one or more elevators should have on each stopping platform the coating of one color and one shade, if there is no other customer requirement.

4.1.19 Welding Places (Welded Sews and Oil Surfaces), made when installing the elevator, should be protected by the coating provided for them in the technical documentation for the elevator.

4.1.20 The ropes must be a dimensional length of one bay and with a purified surface. Dirt and other inclusions on the surface of the ropes are not allowed.

The ends of the ropes should be protected from spinning, and the sections of the cut is made in accordance with 2.1.9 GOST 3241.

4.1.21 Suspended electrical elevator cable must be broken, with closer and installed wires.

Wires of wiring harnesses, laid in the mine and machine room, must be marked. In coordination with the customer, the delivery of measuring length wires is allowed.

4.2 Completeness

4.2.1 The elevator must include:

Elevator equipment in accordance with the specification on the elevator, incl. Spare parts and materials designed for the warranty period of the elevator, tools and accessories (zip) required for the maintenance and repair of the elevator; Spare products for commissioning work during installation (winters) in accordance with their Vedomosti;

Technical documentation sent with elevator and list of parts for replacement in accordance with applications and, accordingly.

In the case of sending several elevators of one type, type, load capacity, speed and execution (various arrangements of the counterweight, passing or non-passing cabin, etc.) for installation on one object or building, the technical documentation is sent in one instance by 5 elevators. Passport, conceptual electrical circuit, electrical connections, mounting (installation) drawing should be sent with each elevator.

4.2.2 Composite parts of the elevator: winch, cab, Mine doors, hydraulic buffer, speed limiter, the tensioning device should be sent in the assembled and adjusted form if there is no other customer requirement.

Brackets of fastening of storey switches, shunts, selection sensors, storey terminal boxes should be sent with attached clamps. Details of the fastening of the guides should be sent in the assembled form with attached clamps.

4.2.3 In disassembled form, it is allowed to send:

Counterweight;

Cabin of a cargo elevator with dimensions in terms of 1500x2000 mm and more;

Cabin of the hospital elevator for buildings of medical and prophylactic institutions;

Doors of the cargo elevators with width of the opening of more than 2000 mm or a height of more than 2600 mm;

Framing (with its own) openings of passenger elevators.

4.3 Marking

4.3.1 Each elevator must be equipped with a signboard made according to GOST 12969, GOST 12970 and GOST 12971.

The elevator plate should indicate:

Name or trademark of the elevator manufacturer;

Lifting equipment marking for the regions of the Far North of the Russian Federation and hard-to-reach areas (for example, mountain, etc.) - according to GOST 15846.

4.4 Packaging

4.4.1 Composite parts of the elevator equipment before packaging must be canned.

Temporary anti-corrosion protection - according to GOST 9.014.

The use of conservation oils for conservation of ropes is not allowed. Their use is allowed to cover the surface of the guide tagging profile.

The preservation of components of elevator equipment should ensure their protection to the first subcast: component parts of the elevator - up to one year, spare parts - up to 2.5 years. The renouncer should hold the elevator owner.

The packaging sheets should indicate: the date and period of the reconstruction, as well as means of temporary corrosion protection.

4.4.2 Preservation and packaging of wires and cables should be carried out with regard to the requirements of GOST 18690, electrical equipment (including bundles) - according to GOST 23216.

4.4.3 Packaging of equipment and technical documentation of the elevator - according to GOST 23170.

The ropes are packaged into a polymer film according to GOST 10354 or on another NTD, coordinated with the GOSGORTECHNADOR, or in waterproof paper according to GOST 8828 and GOST 515.

The rope shown in the bay must be tightly tied up with a soft wire (according to GOST 3282 or other NTD) or a strand of the same rope, or a tape according to GOST 3560 (or other NTD) at least four places that are evenly located around the circle.

4.4.4 Packaging Equipment Equipment in tropical climatic execution must comply with the requirements of GOST 24634, while Tara timber must be impregnated with antiseptic. It is allowed instead of the antiseptation of paint boxes in two layers of the gray paint of the PF-115 brand according to GOST 6465 or other similar paints.

4.4.5 Packaging Equipment Equipment sent to the regions of the Far North of the Russian Federation and hard-to-reach areas - according to GOST 15846.

5 Safety requirements

The safety of elevators is ensured by the implementation of the set of requirements - (except -,), sections, -, of this standard and Pubel Gosgortkhnadzor.

6 Rules acceptance

6.1 Composite parts (equipment) of the elevator (including Zip and Wali) should be subjected to acceptance control by the manufacturer's technical control service in order to determine their suitability for sending to the consumer.

6.2 Remote control of the components of the elevator should be statistical alternatively according to GOST 18242.

Parameters, dimensions, requirements to be controlled, sampling and types of defects should be indicated in the technical documentation for the elevator.

a) control plan:

Control level - II,

Type of control plan - single-stage,

b) acceptance level of winch defective, gearbox (if it is produced as a spare part), elevator doors drive, speed limit, catcher, hydraulic buffer, cab loading devices, shaft doors, cabin doors, springs of responsible destination (buffer springs, brakes, trappers , cab pendants and counterweight, etc.), zip and winters:

2.5% - for significant defects;

6.5%-for insignificant defects.

Acceptance level of defectiveness of other assembly units and equipment parts:

0% - for critical defects;

6.5% - for significant defects.

Production cycle with continuous statistical control - one year.

6.4 Purchased products, materials and raw materials should be subjected to input control according to GOST 24297.

When input control, the low-voltage complete device (HCC) must be checked for operation.

Upon admission from the Customer or consumer elevators of advertising or claims to the quality of the purchase product, the elevator manufacturer during input control should use another more stringent type of control according to GOST 18242.

6.5 Composite parts of the elevator, details and castings produced by other manufacturers should be subjected to an elevator manufacturer to visual control to detect possible damage to this equipment during transportation.

Manufacturer of equipment, details and castings upon receipt of claims from the elevator manufacturer must for 3 days to inform it about the decision to eliminate the defect.

6.6 Acceptance tests of component parts (equipment) elevator

The components of the elevator mentioned in should be subjected to acceptance tests by its manufacturer on programs and methods approved in the prescribed manner.

The size of the sample of the samples of the components of the elevator is set by the elevator manufacturer and is indicated in the technical documentation.

After making a prototype:

Preliminary;

Acceptable;

When developing production - qualifying;

With serial production:

Acceptance tests of component parts of the elevator;

Periodic;

Typical.

6.8 The frequency of testing of the elevator indicated in, the number of elevators to be subjected to these tests, and the number of elevators in the batch, from which the test elevator is selected, must match the table.

6.9 Periodic Tests

6.9.1 Periodic elevator tests are carried out in order to verify the stability of the quality of manufacturing and the possibility of continuing its release.

Periodic tests should include verification of all mandatory requirements established by this standard and Pubel Gosgorekhnadzor.

6.9.2 In case of unsatisfactory results of periodic tests, at least one of the items of the program, repeated tests should be carried out on these points on a twin number of the corresponding components of the elevator taken from the same batch. Results of repeated tests are final.

Table 6.

Test frequency

Number of elevators

The number of elevators in the party, from which the elevators are taken for testing

Preliminary

One-time - after the manufacture of prototypes

All experimental elevator samples, the number of which is determined by the technical assignment to the development

Remote

All experienced samples that have passed preliminary tests.

Qualification

When setting the elevator production of this model

At least 3.

Periodic

At least once every three years

At least 7 *

Every time the design change

At least 3.

* When conducting tests, the manufacturer of the elevators is selected from among the past acceptance control and ready to send to the consumer. When conducting tests on the object of operation, taken from the number made by no more than 18 months before the test.

7 Monitoring methods

7.1 Measurement Requirements

7.1.1 Measurement tools must be believed in accordance with the requirements of GOST 8.002 and GOST 8.513.

Testing equipment must be certified according to GOST 24555, non-standardized measurement tools must undergo metrological certification according to GOST 8.326.

7.2 Preparation for Testing

7.2.1 Before carrying out acceptance and qualification tests of the elevator, tests for the reliability of the winch, drive doors, cabin doors, shaft doors, speed limit, trappers, hydraulic buffers, booth loading devices.

It is allowed not to test the reliability of the equipment borrowed from other elevators, provided that it has been tested earlier and on it, the manufacturer has an rationale for maintaining reliability indicators under operating conditions.

The low-voltage complete device must have a document confirming its reliability.

7.2.2 Prior to periodic tests, the manufacturer must submit materials confirming the reliability indicators of elevators.

Confirmation of reliability indicators is carried out on the basis of a test for the reliability of the elevator or its component parts (equipment) in the period between periodic tests or by the results of operational observations of the work of similar elevators.

Methods and plans for reliability and observations during operation - according to GOST 27.410.

7.2.3 For typical elevator tests, which uses equipment with changes that can affect the technical characteristics of the elevator and / or operation, the tests of each modified equipment should be carried out.

With positive results of testing modified equipment, typical elevator tests are allowed.

7.3 Elevator testing

7.3.1 The tests of elevators should be carried out in accordance with agreed in the prescribed manner.

7.3.1.1 Before the start of the elevator test, the manufacturer must have a "act of technical readiness of the elevator".

Tests should be carried out on the territory of the manufacturer of elevators. The test of the elevator at the operating facility should be coordinated with the Gosgortkhnadzor.

It is not allowed to replace the elevator tests by testing its layout.

When testing group control of elevators at three or more elevators, this system is allowed in the group.

When testing several elevators of the same type and type, it is allowed to determine the quantitative and qualitative characteristics of a single elevator - a typical representative of the group (determined by the elevator developer). The remaining elevators of the group should be checked characteristics that differ from the characteristics of a typical representative.

With unsatisfactory test results for one or more indicators, the resumption of repeated tests is allowed only after establishing the causes of deficiencies and eliminate them.

8 Transportation and storage

8.1 Transportation of equipment equipment is allowed to carry out any kind of transport in accordance with the rules operating on them.

When transporting elevator equipment on the decks of vessels, the elevator manufacturer must take into account the effect of the atmosphere of type III according to GOST 15150.

8.2 Conditions and Terms of Storage and Transportation of Equipment Equipment, Zip and Walkers in packaging and / or preservation of the manufacturer must comply with the table specified in the table.

Table 7.

It is allowed to store elevator equipment under storage conditions 8 according to GOST 15150, both at the manufacturer and the customer for 3 months, with a total storage period of not more than 6 months.

9 Installation and Operation Inspection

9.1 Installation of elevators should be carried out in accordance with the requirements of GOST 22845, Pubel Gosgortkhnadzor and technical documentation for the installation of the elevator.

9.2 The exploitation of elevators should be carried out in accordance with the requirements of Pubel Gosgortkhnadzor and operating instructions.

10 Warranties manufacturer

The manufacturer guarantees the elevator compliance (in general, including composite parts and components) with the requirements of this standard, subject to compliance with the requirements for operation, storage, transportation and installation.

Warranty period - 18 months from the date of signing the "Act of an elevator acceptance".

Appendix A.

1 scheme of conditional designation of passenger elevators

1 - type of elevator; LP - passenger elevator with basic parameters and constructive performance according to GOST 5746;

2 - a group of conditional designation of the basic parameters of the elevator (carrying capacity and rated speed), installed in accordance with the methodology operating in the lift construction of the CIS countries;

3 - An indication of the installation of an elevator - single (in the case notation does not indicate), group (g) from group 2 - 4, 6 elevators (g2 - g4, g6);

4 - the number of elevator stops;

5 -

6 -

7 - indication of the presence of a modulation of the elevator "Transportation of fire units" (P);

8 -

Example of the conditional notationpassenger elevator for residential buildings with basic sizes and structural versions according to GOST 5746, with a carrying capacity of 400 kg, with a rated speed of 0.71 m / s, single installation, with a number of stops 10, performed for operation in the zone of moderately cold climate, placement categories 4 and in the area with the intensity of the seismic effects of 8 points that does not have a mode of operation "Transportation of fire units":

2 scheme of conditional designation of freight elevators

1 - type and type of elevator with parameters, primary sizes and constructive design according to GOST 8823:

Lift cargo regular (lgo);

Freight release elevator (LGV);

Freight elevator usual with monorail (LGOM);

2 - the sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - indication of the gauze of the cabin in terms of the elevator of this carrying capacity - the first (smaller - in the conditional designation does not indicate) or the second (greater) (b);

8 - view of the cab - the passage (Ave.), non-volume (neop.);

9 - climatic performance and category of elevator placement;

10 - An indication of the execution of the elevator (the execution without taking into account the seismic effects in the conditional designation does not indicate), which takes into account the seismic impact (C) with the intensity of 7 - 9 points (C7 - C9);

11 - Designation of this Standard.

Example of the conditional notation a cargo conventional elevator with basic sizes and structural versions according to GOST 8823, with a sequence registration number 922, with a carrying capacity of 1000 kg, at a rated speed of 0.4 m / s, a lifting height of 60 m, with a number of stops 16, from the passage of the second dimension, for Operation in the zone of moderately cold climate and placement category 4:

LGO 922 1000 x 0.4 60 16 B PR Uhl4 GOST 22011-95

3 scheme of the conditional designation of cargo small elevators

1 - type of elevator; LGM - freight elevator small with parameters, basic sizes and constructive design according to GOST 8824;

2 - sequence registration number of the elevator model;

3 - Load capacity, kg;

4 - Nominal speed, m / s;

5 - lifting height, m;

6 - number of stops;

7 - view of the cab - Through (SLE.), Non-cut (narrow);

8 - climatic performance and category of elevator placement;

9 - Designation of this Standard.

Example of the conditional notation a cargo small elevator with parameters, basic sizes and constructive design according to GOST 8824, with a registration number of model 958, a carrying capacity of 100 kg, at a rated speed of 0.4 m / s, a rise in 45 m high, with a number of stops 14, with a non-separated cabin, in Execution for operation in the zone of moderately cold climate and with the category of placement 4:

LGM 958 100 x 0.4 45 NG UHL4 GOST 22011-95

Appendix B.

(mandatory)

* Depending on the type and type of specific elevator, the list of documents for its equipment is specified by the developer.

The technical documentation of the elevator includes the following documents:

Elevator Passport according to Pubel Gosgortecadzor with documents certifying quality: winches, speed limit, doors drive, hydraulic buffer, springs of cabins and counterweight, brake springs, trap springs. NCU passport (stored with the elevator passport);

Mounting drawing (installation drawing, the sample of which is agreed with the Gosgortkhnadzor) (2 copies);

Installation instructions, start-up, regulation and running;

Technical description and instruction manual;

A conceptual electrical circuit with a list of elements (3 copies);

Description of the electric drive and automation (allowed to be supplied as part of a technical description and instruction manual);

Electrical diagram of the electrical components of the elevator control (comes with the NCU);

Electrical diagram of elevator compounds;

Vedomosti Zip and winters;

Drawings of parts for replacement (see application);

Assembly drawings (and specification) Elevator equipment for: speed limiter, hydraulic buffer, winch, gearbox, brake, coupling, tap block, cabin, catcher, automatic door drive, minor door, automatic and manual shaft door locks, wire wiring Machine room, shaft and cabin, counterweight.

Appendix B.

* The parts indicated in the list are designed to replace failed (wear, breakage) during the period of the elevator after the expiration of its warranty period

Pulleys canned.

Brake block assembly.

Spring brakes.

Cabin sliding shoe liner.

Roller (rollers) Cabin shoe.

Insert of the sliding door of the cab of freight elevators.

Passenger lifts shoe shoes.

Roller of the door of the cabin of freight elevators.

Passenger lift carriage carriage roller.

The roller drove the drive of the doors of passenger elevators.

Rubber stop drive doors.

The liner of the sliding shoe counterweight.

Roller carriages of automatic sliding doors of the mine.

Roller Ogrushed Mine Door Castle.

Pulley speed limiter.

Block of tap traction ropes of elevators.

Cleaves of clinorem transmission of cabin drives.

Ring Rubber Cabin Mobile Field Loading Device.

Cabin door drive belt.

Note - The list of parts is specified for a particular elevator by its developer.

Keywords: passenger, cargo and cargo lifts Small elevators, technical requirements, safety requirements, acceptance rules, transportation and storage

GOST 22011-95

Interstate standard

Passenger elevators
And freight

Technical conditions

Interstate Council
According to standardization, metrology and certification

Minsk

1998

Preface

1 Developed by TC 209 "Elevators and Building Lifts"

Submitted by the State Standard of Russia

2 Adopted by the Interstate Council for Standardization, Metrology and Certification (Protocol No. 8-95 of October 12, 1995)

Name of state

Name of the National Standardization Authority

The Republic of Azerbaijan

Azgosstandard

Republic of Belarus

Belstandard.

The Republic of Kazakhstan

Gosstandart of the Republic of Kazakhstan

Kyrgyz Republic

Kyrgyzstandard

The Republic of Moldova

Moldova Standard

the Russian Federation

State Standard of Russia

The Republic of Tajikistan

Tajik State Center for Standardization, Metrology and Certification

Turkmenistan

Home State Inspectorate of Turkmenistan

The Republic of Uzbekistan

UZGOSSTANDART

State Standard of Ukraine

3 Resolution of the Committee of the Russian Federation on Standardization, Metrology and Certification of February 15, 1996 No. 68 Interstate Standard 22011-95 was enacted directly as the State Standard of the Russian Federation from January 1, 1997.

4 instead of GOST 22011-90

5 reprint

Interstate standard

Passenger and freight elevators

Technical conditions

Passenger and Goods Lifts. Specifications.

Date of introduction 1997-01-01

1 AREA OF USE

This standard applies to electric passenger, hospital, cargo and cargo small elevators (hereinafter - elevators).

Standard does not apply to elevators:

Freight paving;

Ship;

Special purpose;

For work in buildings and premises related to categories A and B * in the explosion and fire hazard;

To work in premises with aggressive pairs or gas gases;

To work in conditions of moisture condensation in a mine or machine room, loss of inlet or ice formation on equipment.

* Categories of buildings and premises in the explosion and fire hazard are determined at the design stages of buildings and structures in accordance with the requirements of national fire hazard.

The requirements of this standard are mandatory.

Mandatory requirements for the quality of elevators that ensure their safety for the life, health and property of the population, environmental protection are set out in Section 5.

2 Regulatory references

GOST 8.002-86 GSI. State supervision and departmental control over measurement means. Basic provisions

GOST 8.326-89 GSI. Metrological certification, measuring instruments

GOST 8.513-84 GSI. Verification of measuring instruments. Organization and procedure

GOST 9.014-78 ESZKS. Temporary anti-corrosion protection of products. General requirements

GOST 9.032-74 ESZKS. Paint coatings. Groups, Technical Requirements and Designations

GOST 9.301-86 ESZKS. Metal and non-metallic coatings are inorganic. General requirements

GOST 9.401-91 ESZKS. Paint coatings. General requirements and methods of accelerated resistance tests to the effects of climatic factors

GOST 12.4.026-76 SSBT. Colors Signal and Safety Signs

GOST 27.410-87 Reliability in the technique. Methods for monitoring reliability indicators and control test plans for reliability

GOST 515-77 Paper packing bituminized and tar. Technical conditions

GOST 3241-91 Steel ropes. Technical conditions

GOST 3282-74 Wire steel low carbon overall use. Technical conditions

GOST 3560-73 Steel packing tape. Technical conditions

GOST 5746-83 Electric passenger elevators. Main parameters and dimensions

GOST 6465-76 EMALE PF-115. Technical conditions

GOST 8823-85 Electric freight elevators. Main parameters and dimensions

GOST 8824-84 Electric freight elevators. Main parameters and dimensions

GOST 8828-89 Paper base and two-layer waterproof paper packaging. Technical conditions

GOST 10354-82 Polyethylene film. Technical conditions

GOST 12969-67 Plates for machinery and appliances. Technical requirements

GOST 12970-67 Round signs for machines and appliances. Dimensions

GOST 12971-67 Plates rectangular to machine and appliances. Dimensions

GOST 14192-96 cargo marking

GOST 15150-69 Machines, appliances and others technical products. Versions for different climatic regions. Categories, conditions of operation, storage and transportation in terms of exposure to climatic factors of the external environment

GOST 15846-79 Products sent to the regions of the Far North and hard-to-reach areas. Packaging, Marking, Transportation and Storage

GOST 18242-72 Statistical acceptance control alternatively. Control plans

GOST 18690-82 cables, wires, cords and cable fittings. Marking, Packaging, Transportation and Storage

GOST 22845-85 Electric passenger and freight elevators. Rules of organization, production and acceptance of installation work

GOST 23170-78 Packaging for mechanical engineering products. General requirements

GOST 23216-78 Electrotechnical products. General requirements for storage, transportation, temporary anti-corrosion protection and packaging

GOST 23511-79 Industrial radio interference from electrical devices operated in residential buildings or electrical networks connected to their electrical networks. Norms and measurement methods

GOST 24297-87 Input control of products. Basic provisions

GOST 24555-81 SGIP. The procedure for certification of test equipment. Basic provisions

GOST 24634-81 Wooden boxes for products supplied for export. General technical conditions

GOST 28911-91 elevators and small freight elevators. Controls, alarms and additional devices

"Rules for the device and safe operation of elevators" of national technical supervision authorities for the safe operation of elevators

Snip 21-01-97 Construction rates and rules. Fire safety of buildings and structures

3 Main parameters and sizes

The main parameters and sizes of electric passenger and hospital elevators - according to GOST 5746.

The main parameters and dimensions of electrical freight elevators - according to GOST 8823.

The main parameters and the size of electrical cargo small elevators - according to GOST 8824.

The symbol of elevators is given in Appendix A.